The primary power feed for the repeater is via a
dedicated 200 amp 240/110 volt single phase PG&E service. The primary
breaker is sized at 50 amps. Emergency power is obtained from
a 400 kw Propane fed generator that is common to other commercial
equipment located on the mountain. The generator is programmed to
run at load for 20 minutes once a week. Baycom provides it's own
switching logic so that power transfers to the generator are
only permitted when a loss of PG&E is also detected. The sequencing
of power is timed for each building and presently set for transfers
to occur 9 and 10 seconds after the generator is up to voltage
with the commercial equipment loads on line. For other than the
weekly load test the generator is programmed to remain on for about
5 min after PG&E comes back on line to insure that PG&E power is
stabilized.
400 Kw Emergency Generator
Generator Front Panel
Propane Tank for Emergency Generator
Master AC Power Monitor Panel